Hospital has initiated several power conservation methods to conserve electricity.

Electrical Installation

Changes to Electrical Installation to Conserve Power

1) Street light
OLD system 150W × 120nos — 18KW/hour. In 10 hours average energy consumption 180KW.
Present system 150w was replaced with 30W: 30W × 120nos — 3.6KW/hour. In 10 hours average energy consumption 36KW.

2) Tube light
Old system 40W × 2000nos — 80KW. In 10 hours average energy consumption 800KW.
Present system 40W was replaced with 20W: 20W × 2000nos — 40KW. In 10 hours average energy consumption 400KW.

3) Dryers in Laundry
60KW heating elements was replaced by 30KW.

HVAC Installation

Changes to HVAC Installation to Conserve Power

Sr. NoDescriptionAction takenEnergy savingsEnergy savings per dayEnergy saving per year 364 days at ₹8/unit
1Cooling tower no1, Cooling tower no2, Cooling tower no3Cooling tower has been replace - 2nos of 10 hp/7.5 kw motor to 1no motor of 12.5hp/10kw.5 Kw/HrAn average working of cooling tower per day 12 hrs = 60 kw/day21,840 kw/year — Rs 1,74,720
2Radiology 2nos of AHUs 35TR with 12.5hp/10kw motor & 10hp/7.5 kw motor working contentiously in day timeInter connected the ducting of 2 AHUs and switched off one AHU permanently.7.5 kw/HrAn average working of AHU per day is 12 hrs = 90 kw/day32,760 kw/year — Rs 2,62,080
3CTVS ICU and neuro ICU100% Fresh air system converted into 70% Fresh air 30% Recirculated air system without effecting the standards. Disconnected 10hp/7.5 kw exhaust blower and Heat Recovery wheel of around 0.5 kw.8 kw/hrICU works 24 hrs per day — 192 kw/day69,888/year — Rs 5,59,104
4MS.OT - 4nos100% Fresh air system converted into 70% Fresh air 30% Recirculated air system without effecting the standards. Disconnected 1hp/.75 kw exhaust blower and Heat Recovery wheel of around 0.25 kw.1 kw/hrOT is working around 12 hrs per day — 12 kw/day4,368 kw/year — 34,944
5VFDs for Cath lab AHU-30TR-12.5HP/10KW, CCU AHU-30TR-10HP/7.5KW, Labor room AHU-30TR-10HP/7.5KW, CTVS ICU-15HP/12.5KW, Neuro ICU-15HP/12.5KWBy introducing the VFDs in different location AHUs the efficiency improved in AHUs and an average and overall 0.5 kw has been saved.3 kw/hrAn average working AHUs all together 15 Hrs/day — 45 kw/day16,380 kw/year — 1,31,040